Description

Voltage

600V or less


Construction

Sino-cables XHHW-2 type aluminum conductors are annealed AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture and high-heat resistant black cross-linked polyethylene. Conductor sizes AWG 2 and larger listed and marked sunlight resistant in black only.

Copper conductor is also available.


Standard

XHHW-2 conductors meet or exceed UL Standard 44 .Federal Specification A-A-59544, and requirements of the NEC Type XHHW-2 meets and exceeds all construction requirements of ICEA S-95-658(NEMA WC 70)-Non shielded 0-2kv Cables, with testing frequencies based on UL requirements.


Features

1.-40℃----90℃

2.High-Heat and Moisture and Sunlight Resistant.

3.VW-1 or higher required by UL.


Applications

1.XHHW-2 conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electric Code(NEC).

2.May also be used in wet or dry locations at temperatures not to exceed 90℃.

3.Voltage rating for RW90 cable is 600V.


Package

steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.  


W E I G H T S.  M E A S U R E M E N T S
CONDUCTOR SIZE
(AWG or kcmil)
INSULATION
THICKNESS
(mils)
NOMINAL O.D.
(mils)
ALLOWABLE
AMPACITIES*
APPROXIMATE
     NET WEIGHT
   PER 1000ft(Ibs)
60℃75℃90℃
84522830404531
64526340506043
44530755657567
245362759010087
15541385100115109
1/055450100120135133
2/055490115135150162
3/055537130155175201
4/055589150180205246
25065654170205230297
30065704190230255352
35065750210250280402
40065793225270305454
50065870260310350555
60080980285340385680
700801041310375420783
750801072320385435832
10008012243754455001091
* Ampacities for not more than three conductors in raceway, based on ambient temperature of 30°C per Table 310-16 of the 2005 National Electrical Code (NFPA 70-1990).
  60 °C - When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors.
  75 °C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.

  90°C - XHHW wet or dry locations for ampacity adjustment purposes using NEC section 310.1.      

* All values are nominal and subject to correction.