Home > Products > Aluminum Alloy GB IEC Standard > YJLHV
Description

Voltage

0.6KV----35KV


Construction

Sino-cables YJLHV type is constructed with AA-8000 series aluminum alloy, compact stranded conductor. The conductor is extruded with XLPE(cross-linked polyethylene) insulation. The insulated conductors are cabling together with non-hygroscopic fillers inside for round shape and reinforcement tape for added strength and conformity. A PVC outer jacket covers the entire assembly.    


Standard

GB/T 12706; GB/T 31840; IEC60502, or other standards required by customers.


Features

1.the operating temperature: -40℃----90℃.

2.good bendability, high elongation and flexibility, low spring-back, excellent properties of creep resistance, anti-corrosion and anti-oxidant, stable connection.

3.fire resistant as NH, fire retardant as ZR, low smoke halogen free as WDZ, or other requirements by customers.

4.with less budget cost and superior combination performance, YJLHV type AA8000 aluminum alloy cable replaces copper power cable overwhelmingly.


Applications

1.YJLHV Type cable is specially designed for the common residence, commercials and industrial buildings, such as civilian constructions, hospitals, schools, etc. It’s also widely applied in the circumstances without armored mechanical protection, such as office building, hotel, plaza, factory lighting and other feeder circuits of electrical equipment. 

2.Suitable for installation of both indoor and outdoor environment, uprightness, bracket, being along wall and direct burial.


0.6/1KV YJLHV  Physical index


Nominal C.S.A. Of conductor
     (mm2)
Approx. overall diameter of cable (mm)Approx. Weight of cable (KG / KM)
1
core
2
core
3
core
4
core
5
core
3+1
core
3+2
core
4+1
core
1
core
2
core
3
core
4
core
5
core
3+1
core
3+2
core

4+1

core

1010.916.717.518.920.418.519.620.198233261305369297341354
1612.018.919.921.623.420.922.222.8126289342415507393457484
2513.621.923.225.227.524.325.826.6171386483580711557626665
3514.624.125.627.830.726.327.629.1211490603728907682781854
5016.327.429.132.135.230.232.132.527358076297711988589961101
7018.030.832.936.340.034.136.238.1351784103113411652113413111473
9519.534.036.239.844.037.940.442.3436981129417822103149217631899
12021.337.640.344.349.342.445.447.55311230158821362578189321622388
15023.341.844.849.554.746.248.951.36481475201125903217226125982949
18525.246.149.254.760.351.053.757.87791631247632013906287734173743
24028.052.055.461.468.157.560.564.49742389316640574895357238234578
30030.356.360.267.174.262.866.472.311882786368148786072433448595659
40034.163.868.475.384.570.674.679.415453691490663517981565763977314
50037.670.875.884.592.678.583.688.519064510607979039798702880089153
63041.979.084.894.6104.885.590.497.723875769770410110124638663989110898


0.6/1KV YJLHV  Ampacity


Nominal C.S.A. Of conductor (mm2)Dia.of conductor
(mm)
Insulation thickness
(mm)
D.C. Resistance at 20℃
(Ω / KM)
Resistance of insulation
(M Ω / KM )
Current rating
In the air (A)Direct in soil (A)
103.80.7≤ 3.080≥ 5.23 × 1045563
164.80.7≤ 1.910≥ 4.31 × 1047181
256.00.9≤ 1.200≥ 4.44 × 10494105
357.00.9≤ 0.868≥ 3.79 × 104116124
508.41.0≤ 0.641≥ 3.55 × 104146152
7010.01.1≤ 0.443≥ 3.35 × 104180185
9511.61.1≤ 0.320≥ 2.90 × 104218223
12013.01.2≤ 0.253≥ 2.82 × 104256252
15014.61.4≤ 0.206≥ 2.94 × 104295285
18516.21.6≤ 0.164≥ 3.03 × 104338323
24018.41.7≤ 0.125≥ 2.83 × 104398375
30020.61.8≤ 0.100≥ 2.63 × 104459423
40023.82.0≤ 0.0778≥ 2.59 × 104547485
50026.52.2≤ 0.0605≥ 2.56 × 104625547
63030.02.4≤ 0.0469≥ 2.49 × 104714608


In the air: 40℃ Direct in soil: 25℃, the coefficient of Soil thermal resistance 1.2Km/w