Home > Products > Aluminum Alloy GB IEC Standard > YJLHVS2
Description

Voltage

0.6KV----35KV


Construction

Sino-cables YJLHVS2 type is constructed with AA-8000 series aluminum alloy, compact stranded conductor. The cable consists of one, two, three or four insulated phase-identified conductors plus an insulated grounding conductor inside interlocked aluminum alloy armor. The entire assembly is covered with a PVC jacket for added durability and protection.    


Standard

GB/T 12706; GB/T 31840; IEC60502, or other standards required by customers.


Features

1.the operating temperature: -40℃----90℃, Conductor insulation is free of harmful heavy metals in compliance with RoHS.

2.good bendability, high elongation and flexibility, low spring-back, excellent properties of creep resistance, anti-corrosion and anti-oxidant, stable connection, sunlight resistant.

3.fire resistant as NH, fire retardant as ZR, low smoke halogen free as WDZ, or other requirements by customers.

4.Bending radius is only 7 times of the outer diameter of the cable and lightweight, which makes installation easier.

5.Quick, easy one-step installation designed to save time, money, and energy, YJLHVS2 type AA8000 aluminum alloy cable replaces copper power cable overwhelmingly.


Applications

1.Sino-cables YJLHVS2 type can be applied to Branch, feeder and service power distribution under high ambient temperature in commercial, industrial, institutional, and multi-residential buildings.

2.YJLHVS2 is also suitable for direct burial applications, installation in concrete and where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.

3.designed for both above-ground and underground applications in dry or wet locations; Power, lighting, control, and signal circuits;Fished or embedded in plaster;Concealed or exposed installations;as aerial cable on a messenger;Installation in cable tray and approved raceways.

4.Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Location.


0.6/1KV YJLHVS2  Physical index


Nominal C.S.A.
of conductor
(mm²)
Approx. overall diameter of cable (mm)Approx. weight of cable(KG / KM)
2
core
3
core
4
core
5
core
3+1
core
3+2
core
4+1
core
2
core
3
core
4
core
5
core
3+1
core
3+2
core
4+1
core
1022.223.124.425.924.025.125.5385448514587492534557
1624.425.427.128.926.427.728.3484566647737606687705
2527.428.730.733.029.231.332.3595707854984795889946
3529.631.133.636.231.833.334.97048641014119798410751123
5032.934.637.740.935.937.739.2885107513091575119313091407
7036.338.442.145.740.042.144.91086135317552007154717591910
9539.341.745.849.943.846.348.21284170521312511189621842316
12043.145.850.455.248.351.553.21602198825743044228826962887
15047.350.555.760.852.155.058.01913248130933732274231023413
18551.654.960.766.456.960.064.32272295337784477334839464262
24057.761.367.874.263.466.870.62739363146785596409346315216
30062.466.173.280.468.872.977.63330434156246764488156406215
40070.174.182.290.376.581.186.64189563171898673621371208862
50076.981.990.699.784.490.095.750906879878410505763686179639
63086.190.9100.7110.991.998.4104.562038449106531295293731031911708


0.6/1KV YJLHVS2  Ampacity


Nominal C.S.A. of conductor (mm²)Dia. of conductor(mm)Insulation thickness(mm)D.C. Resistance
at 20℃ (Ω / km)
Resistance of insulation
(M Ω / km)
Current rating(A)
In the airDirect in soil
103.80.7≦ 3.080≧ 5.23 × 1045562
164.80.7≦ 1.910≧ 4.31 × 1047381
256.00.9≦ 1.200≧ 4.44 × 10497105
357.00.9≦ 0.868≧ 3.79 × 104119124
508.41.0≦ 0.641≧ 3.55 × 104149148
7010.01.1≦ 0.443≧ 3.35 × 104184181
9511.61.1≦ 0.320≧ 2.90 × 104223218
12013.01.2≦ 0.253≧ 2.82 × 104260247
15014.61.4≦ 0.206≧ 2.94 × 104300280
18516.21.6≦ 0.164≧ 3.03 × 104343318
24018.41.7≦ 0.125≧ 2.83 × 104403370
30020.61.8≦ 0.100≧ 2.63 × 104464428
40023.82.0≦ 0.0778≧ 2.59 × 104571499
50026.52.2≦ 0.0605≧ 2.56 × 104631530
63030.02.4≦ 0.0469≧ 2.49 × 104725625


In the air: 40℃ Direct in soil: 25℃, the coefficient of Soil thermal resistance 1.2Km/w